Sunday, February 14, 2010

BASIC CONCEPT IN ELECTRICAL DESIGN

RECEPTACLES AND WIRING DEVICES


ELECTRICAL CONDUCTORS AND INSULATORS


Electrical Conductors are substances that offer a very low resistance to current flow.


Insulators are substances that offer a very high resistance to current flow.



List of some good electrical conductors:


Silver
Zinc
Copper
Platinum
Aluminum
Iron
Nickel
Tin
Brass
Lead


List of some insulating materials:

Rubber
Asbestos
Porcelain
Thermoplastics
Varnish
Paper
Slate
Oils
Glass
Wax
Mica
Dry air
Latex



WIRES AND CABLES



Wires are those electrical conductors which are 8 mm2 (AWG no. 8) or smaller, while cables are those larger than the wires. They are either solid or stranded.



Stranded wire - consists of a group of wires twisted to form metallic string. The total circular-mil area of a stranded wire is found by multiplying the circular mil area of each strand by the total number of strand.



Cord is the term given to an insulated stranded wire.




CIRCULAR MIL. This is the unit of cross section in the American wire gauge. The term “mil” means one-thousandth of an inch (0.001 in.). It is the area of a circular wire having a diameter of one mil. To find the number of circular mils in a circle of a given diameter, we have to square the number of mils in the diameter.



Area in circular mil = ( diameter in mils )2

1 inch = 1,000 mils

MCM = 1,000 circular mils




SQUARE MIL. It is the area of a square having its side equal to 1 mil.

Square mil = ( sides )2 = ( 1 mil )2 = ( 0.001 in.)2 = 1 x 10-6 in.2

Square mil = 0.7854 x circular mils




CONDUCTOR AREAS:


CONVERSION FACTOR


Square inch = square mil x 0.000001

Square mil = square inch x 1,000,000

Square mil = circular mils x 0.7854

Circular mil = square mils x 1.273

Millimeter = inches x 25.4

Square mm = circular mils x 0.0005067


















DIFFERENT TYPES OF CABLES



1. Armored Cable. This type of cable, the type AC is a fabricated assembly of insulated conductors enclosed in flexible metalsheath. Armored cable is used in both exposed and concealed work.



2. Metal Clad Cable. Cable of the type MC is a factory assembled cable of one or more conductors, each individually insulated and enclosed in a metallic sheath of interlocking tape, or a smooth or corrugated tube. This type is used specifically for services, feeders, branch circuits, either exposed or concealed and for indoor or outdoor work.



3. Mineral Insulated Cable. This type of cable, type MI, is a factory assembly of one or more conductors insulated with a highly compressed refractory mineral insulation and enclosed in liquid-tight and gas-tight continuous copper sheath. The type MI is used in dry, wet or continuously moist location as service, feeders or branch circuit.



4. Nonmetallic Sheathed Cable. Types NM and NMC are factory assembled two or more insulated conductors having a moisture-resistant outer sheath, flame-retardant and non-metallic material. These types are used specifically for one or two dwelling not exceeding 3 storey buildings.



5. Shielded Nonmetallic Sheathed Cable. This type of cable, the type SNM, is a factory assembly of two or more insulated conductors in an extruded core or moisture-resistant and flame-retardant material, covered with an overlapping spiral metal tape. This type is used in hazardous locations and in cable trays or in raceways.



6. Service Entrance Cable. This is a single conductor or multiconductor assembly provided with or without an over-all covering, primarily used for services and of the types SE and USE.



7. Underground Feeder and Brach Circuit Cables. This type of cable, the type UF cable is a moisture-resistant cable used for underground, including direct burial in the ground, as feeder or branch circuit.



8. Power and Control Tray Cable. Type TC cable is a factory assembly of two or more insulated conductors with or without associated bare or covered grounding under a metallic sheath. This is used for installation in cable trays, raceways or where supported by a messenger wire.



9. Flat Cable Assemblies. This is an assembly of parallel conductors formed integrally with an insulating material web designed specifically for field installation in metal surface raceway. Cables of this type are the types FC.



10. Flat Conductor Cable. This type of cable, type FCC consists of three or more flat conductors placed edge to edge, separated and enclosed within an insulating assembly. This used for general purpose, appliance branch circuits and for individual branch circuits specifically on hard, smooth, continuous floor surfaces, etc.



12.Medium Voltage Cables. MV cable is a single or multiconductor solid dielectric insulated cable rated 2,001 volts or higher and is used for power systems up to 35,000 volts. The MV cables are of different types and characteristics.




RACEWAYS



Raceways are channels designed for holding wires, cables or bus-bars, which are either made of metal or insulating materials. The common types of raceways in household wiring are the a) conduits, b) connectors, and c) others.



a) Conduits


Conduits, pipes or tubings are the most common electrical raceway.


According to the type of materials used, conduit maybe classified as either metallic such as steel pipes or nonmetallic such as PVC, and the like.


According to its make, conduits maybe classified as: rigid metal, flexible metal, rigid nonmetal and flexible nonmetal.


b) Connectors


A connector is a metal sleeve usually made of copper that is slipped over and secured to the butted ends of conductors in making joint. A connector is also called a splicing sleeve.


c) Other Raceways


Aside from the conduits and connectors there are still numerous types and kinds of raceways, among these are the a) conduit couplings, elbows and other fittings; b) conduit supports, such as clamps, hangers,etc; c) cable trays, cablebus; d) metal raceways;e) nonmetal raceways.



OUTLETS, RECEPTACLES and other WIRING DEVICES




outlets. An outlet is a point in the wiring system at which current is taken to supply utilization equipment. The kinds of outlets are: convenience outlet or attachment cap, lighting outlet, and receptacle outlet.



A convenience outlet or attachment cap is a device which by insertion in a receptacle, establishes connection between the conductor of the flexible cord and the conductors connected permanently to the receptacle.



A lighting outlet is an outlet intended for direct connection of a lampholder, a lighting fixture, or a pendant cord terminating in a lampholder.



A receptacle outlet is an outlet where one or more receptacles are installed.





TYPES OF WIRES



A. TYPES T, TW, THW


The most ordinary type of plastic insulated wire is the “type T”. It may be used only in dry locations. Some manufactures no longer make the ordinary Type T, instead produce Type TW, which is identical in appearance, but may be used in wet or dry locations. Also available is Type THW, is similar to Type TW but withstand a greater degree of heat, and consequently has a higher ampacity rating in the larger sizes.



B. TYPES THHN, THWN


These are comparatively new types of wire, consisting of the basic Type THH and THW but with less thermoplastic insulation, and with a final extruded jacket of nylon. Nylon has exceptional insulating qualities and great mechanical strength, all of which results in a wire which is smaller in diameter than ordinary Types T, TW, TW of corresponding size.



C. TYPE XHHW


In appearance, it resembles Types T, TW, THW but because of somewhat thinner layer of insulation, the over-all diameter is smaller. The insulation is “cross-linked synthetic polymer,” which has an extraordinary properties as to insulating value, heat resistance, and moisture resistance. It may be used in dry or wet locations. While at present, it is an expensive wire, it would be no surprise if in due course of time, this one single type will replace all the many types and subtypes of Type T or R now recognized by the Code.



D. RUBBER-COVERED WIRE



It consists of copper conductor, tinned to make it easier to remove the insulation, and for easy soldering. Over the copper is a layer of rubber, the thickness of which depends on the size of the wire. Then follows an outer fabric braid which is saturated with moisture-and-fire-resistant compounds; if it is set on fire with a blowtorch, the flame dies out when the torch is removed.



E. OTHER TYPES


Other types such as the basic Type R, which is suitable for only in dry locations, is no longer being made. The most ordinary kind is Type RHW, which may be used for dry or wet locations. Types RH and RHH have insulation which withstands more heat and therefore have a higher ampacity in the larger size. They may be used only in dry locations.




KINDS OF LOCATIONS



DAMP LOCATION


Partially protected locations under canopies, marquees, roofed open porches, and like locations, and interior locations subjected to moderate degree of moisture, such as some basements, some barns, and some cold-storage warehouses.



DRY LOCATION


A location not normally subject to dampness or wetness. A location classified as dry may be temporarily subject to dampness or wetness, as in the case of a building under construction.



WET LOCATION


Installations underground or in concrete slabs or masonry in direct contact with the earth, and location subject to saturation with water or other liquids, such as vehicle washing areas, and locations exposed to weather and unprotected.




HAZARDOUS (CLASSIFIED) LOCATIONS


Locations where fire or explosion hazards may exist due to flammable gases or vapors, flammable liquids, combustible dust, or ignitible fibers or flyings.


1. Class I Locations. Class I locations are those in which flammable gases or vapors are or may be present in the air in quantities sufficient to produce explosive or ignitible mixtures.



a) Class I, Division 1. A class I, Division 1 location is a location: I) in which igntible concentrations of flammable gases or vapors can exist under normal operating conditions; or ii) in which ignitible concentrations of such gas vapors may exist frequently because of repair or maintenance operations or because of leakage; or iii) in which breakdown or faulty operation of equipment or processes might release ignitible concentrations of flammable gases or vapors, and might also cause simultaneous failure of electric equipment.



b) Class I, Division 2. A Class I, Division 2 location is a location: I) in which volatile flammable liquids or flammable gases are handled, processes, or used, but in which the liquids, vapors, or gases will normally be confines within closed containers or closed systems from which they can escape only in case of accidental rupture or breakdown of such containers or systems, or in case of abnormal operation of equipment; or ii) in which ignitible concentrations of gases or vapors are normally prevented by positive mechanical ventilation, and which might become hazardous through failure or abnormal operation of the ventilating equipment; iii) that is adjacent to Class I, Division 1 location, and to which ignitible concentrations of gases or vapors might occasionally be communicated unless such communication is prevented by adequate positive ventilation from a source of clean air, and effective safeguards against ventilation failure are provided.



Class II Locations. Class II locations are those that are hazardous because of the presence of combustible dust.


a) Class II, Division 1. A class II, Division 1 location is a location: I) in which combustible dust is in the air normal operating conditions in quantities sufficient to produce explosive or ignitible mixtures; or ii) where mechanical failure or abnormal operation of machinery or equipment might cause such explosive or ignitible mixtures to be produced, and might also provide a source of ignition through simultaneous failure of electric equipment, operation devices, or from other causes; or iii) in which combustible dusts of an electrically conductive nature may be present in hazardous quantities.



b) Class II, Division 2. A Class II, Division 2 location is a location where combustible dust is not normally in the air in quantities sufficient to produce explosive or ignitible mixtures, and dust accumulations are normally insufficient to interfere with the normal operation of electrical equipment or other apparatus, but combustible dust may be in suspension in the air as a result of infrequent malfunctioning of handling or processing equipment and where combustible dust accumulations on, in, or in the vicinity of the electrical equipment may be sufficient to interfere with the safe dissipation of heat from electrical equipment or may be ignitible by abnormal operation or failure of electrical equipment.



3. Class III Locations. Class III locations are those that are hazardous because of the presence of easily combustible fibers or flyings, but in which such fibers or flyings are not likely to be in suspension in the air in quantities sufficient to produce ignitible mixtures.



a) Class III, Division 1. A Class III, Divisions 1 location is a location in which easily ignitible fibers or materials producing combustible flyings are handled, manufactured, or used.



b) Class III, Division 2. A Class III, Division 2 location is a location in which easily ignitible fibers are stored or handled.





ELECTRIC CIRCUITS IN BUILDING

* SERVICES *


No. of Service:


A building or other structure served shall be supplied by only one service.



*EXCEPTIONS*


1. For fire pump where a separate service is required.


2. For emergency electrical system where a separate service is required.


3. Multiple-occupancy building


4. Capacity requirements. Two or more services shall be permitted:



a) Where the capacity requirements are in excess of 2,000 amperes at a supply voltage of 600 volts or less; or


b) Where the load requirements of a single-phase installation are greater than the serving agency normally supplies through one service; or


5. Building of large area ( 10,000 m2 or more Total Area ).


6. For different voltage characteristics, such as for different voltage, frequencies, or phases, or for different uses, such as for different rate schedules.



THE OVERHEAD SERVICE-DROP CONDUCTOR




This is the overhead service conductor from the last pole or other aerial support to and including the splices if any, connecting the service entrance conductors at the building or other structure.



SIZE AND RATING:


a) General. Service drop shall have sufficient ampacity to carry the load without a temperature rise detrimental to the covering or insulation of the conductors and shall have adequate mechanical strength.



b) Minimum size. The conductors shall not be smaller than 8 mm2 copper, 14 mm2 aluminum or copper-clad aluminum.



CLEARANCES:


a) Above Roofs. Conductors shall have a vertical clearance of not less than 2,500 mm from the roof surface.


b) Vertical clearance from Ground.


  • 3,100 mm - at the electric service entrance to buildings, or at the drip loop of the building electric entrance, or above areas or sidewalks

  • 3,700 mm - for those areas listed in the 4,600 mm classification when the voltage is limited to 600 volts to ground.

  • 4,600 mm - over residential property and driveways, and those commercial areas not subject to truck traffic.

  • 5,500 mm - over public streets, alleys, roads, parking areas subject to truck traffic, driveways on other than residential property, and other land transversed by vehicles such as cultivated, grazing, forest, and orchard.


UNDERGROUND SERVICE-LATERAL CONDUCTOR




This is the underground service conductor between the street main, including any risers at a pole or other structure or from transformers, and the first point of any connection to the service-entrance conductors in a terminal box or meter or other enclosure with adequate space, inside or outside the building wall.



INSULATION. Service-lateral conductor shall withstand exposure to atmospheric and other conditions of use without detrimental leakage of current.



*EXCEPTIONS*


A grounded conductor shall be permitted to be uninsulated as follows:


a) Bare copper used in a raceway.


b) Bare copper for direct burial where bare copper is judged to be suitable for the soil conditions.


c) Bare copper for direct burial without regard to soil conditions where part of cable assembly identified for underground use.


d) Aluminum or copper-clad aluminum without insulation or covering where part of a cable assembly identified for underground use in a raceway or for direct burial.



SIZE AND RATING


a) General. Service lateral conductors shall have sufficient ampacity to carry the current for the load and shall have adequate mechanical strength.


b) Minimum Size. The conductors shall not be smaller than 5.5 mm2 copper or 8.0 mm2 aluminum or copper-clad aluminum.


Where two to six service disconnecting means in separate enclosures supply separate loads from one service drop or lateral, one set of service entrance conductors shall be permitted to supply each or several such service equipment enclosures.


EXCEPTION: For installations to supply only limited loads of a single branch circuit such as small polyphase power, controlled water heaters and the like, they shall not be smaller than 3.5 mm2 copper or 5.0 mm2 aluminum or copper-clad aluminum.



SERVICE ENTRANCE



Service is defined as the portion of the supply which extends from the street main duct or transformer to the service switch or switchboard of the building supply.


-it is the conductor and equipment for delivering energy from the electricity supply system to the wiring system of the premises served.



TYPES:



1. Overhead Service Entrance


The most common type of service entrance employed by the power companies supplying electricity which is either a 2, 3 or 4-wire connection. Generally, the overhead service cable between the building property line and the supply point is supplied by electric company to a limit of 30 meters.



2. The Underground Service Entrance


The underground service entrance consists of a raceway conduit extending from the building to the property line where it is tapped to the main. The type of cable recommended is the underground service entrance cable commonly referred to as USE.





SERVICE - ENTRANCE CONDUCTORS




No. of Service-Entrance Conductor Sets

Each service drop or lateral shall supply only one set of service-entrance conductors.



*EXCEPTIONS:


1. Buildings with more than one occupancy.


2. Where two to six service disconnecting means in a separate enclosures are grouped at one location and supply separate loads from one service drop or lateral.



SIZE AND RATING: Service entrance conductors shall be of sufficient size to carry the computed loads.


Ungrounded conductors shall not be smaller than:


1. 100 A ---- For one family dwelling with six or more 2-wire branch circuits.

2. 60 A ---- For one family dwelling with an initial computed load of 10 kVA above.

3. 40 A ---- For other loads.



EXCEPTIONS:


1. For loads consisting of not more than 2 - wire branch circuits, 5.5 mm2 copper or 8.0 mm2 aluminum or copper-clad aluminum.


2. By special permission, for loads limited by demand or by the source of supply, 5.5 mm2 copper or 8.0 mm2 aluminum or copper-clad aluminum.


3. For limited loads of single branch circuit, 3.5 mm2 copper or 5.5 mm2 aluminum or copper-clad aluminum.



INSTALLATION OF SERVICE CONDUCTORS


Service entrance conductors shall be installed in accordance with the applicable requirements of this Code covering the type of wiring method used and limited to the following methods:


1. Open-wiring on insulators

2. Rigid Metal Conduit (RMC)

3. Intermediate Metallic Tubing (IMT)

4. Electrical Metallic Tubing (EMT)

5. Service-Entrance Cables

6. Wireways

7. Busways

8. Auxiliary gutters

9. Rigid Non-Metallic Conduit (RNMC)

10. Cable Bus

11. Mineral-Insulated Metal-Sheated Cable

12. Type MC Cables



PROTECTION:


Service entrance conductors subjected to physical damage shall be protected in any of the following ways or methods:


1. By RMC

2. By IMC

3. By RNMC suitable for the location

4. By EMT

5. Type MC cable or other approved means



THE SERVICE EQUIPMENT-DISCONNECTING MEANS



GENERAL:

The service-disconnecting means shall be provided to disconnect all conductors in a building or other structures from the service-entrance conductor.


NUMBER OF DISCONNECTING MEANS:

The service disconnecting means for each set or each subset of service entrance conductor shall consist of not more than six switches or six circuit breakers mounted in a single enclosure, or in a switchboard.



LOCATION:

The service disconnecting means shall be installed either inside or outside the building or other structure at a readily accessible location nearest the point of entrance of the service entrance conductor



RATING:

The service disconnecting means shall have a rating of not less than the load to be carried. In no case shall the rating be lower than specified through:


1. One circuit installation -- The service disconnecting means shall have a rating of not less than 15 amperes.


2. Two circuit installation -- The service disconnecting means shall have a rating of not less than 30 amperes.


3. One family dwelling -- The service disconnecting means shall have a rating of:


60 A -- where the initial computed loads is 10 kVA or more

100 A -- where the initial installations consist of six or more 2-wire branch circuit.



4. Others -- For all other installations, the service disconnecting means shall have a rating of not less than 40 amperes.



NOTES:

The service disconnecting means shall simultaneously disconnect all ungrounded conductors and shall be capable of being closed on a fault equal to or greater than the maximum available short-circuit current.


Service entrance conductor shall have a short-circuit protective device in each ungrounded conductors.


Fuses shall have an Interrupting Rating no less than the maximum available short circuit current in the circuit at their supply terminals.


Circuit breakers shall be free to open in case the circuit is closed on an overload. Circuit breakers shall have an interrupting rating not less than the maximum available short-circuit current at its supply terminals.



THE CIRCUIT BREAKER AND THE FUSE



A circuit breaker is an overcurrent protective device also designed to function as a switch. It is equipped with an automatic tripping device to protect the branch circuit from overload and ground fault.



A fuse is also an overcurrent protective device with a circuit opening fusible element which opens when there is an overcurrent in the circuit. It is considered as the simplest and the most common circuit protective device used into the house wiring connection.



Advantages of circuit breaker over a fuse


1. The circuit breaker acts as a switch aside from its being an overcurrent device.


2. When there is an overcurrent, the circuit breaker trips automatically and after correcting the fault, it is ready to be switched on again, unlike the fuse which has to be discarded and replaced after it is busted.


Advantages of fuse over a circuit breaker


1. One of its major advantage is its reliability and stability. It can stay on its position for years and act when called on to act as designed, unlike the circuit breaker which requires proper maintenance and periodic testing to keep it into a tip-top condition.


2. The cost of a fuse is less than that of a circuit breaker.


Standard Ampere Ratings of Fuses and Inverse time circuit breakers


15, 20, 25, 30, 40, 45, 60, 70, 80, 90, 100, 110, 125, 150, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000 and 6000


Fuses, circuit breakers or combinations shall not be connected in parallel.

Exception: Circuit breakers or fuses, factory assembled in parallel, and approved as a unit.





Position of Knife Switches


a) Single-throw Knife Switches. Single-throw knife switches shall be so placed that gravity will not tend to close them. Single-throw knife switches, approved for use in the inverted position, shall be provided with a locking device that will ensure that the blades remain in the open position when so set.



b) Double-throw Knife Switches. Double-throw knife switches shall be permitted to be mounted so that the throw will be either vertical or horizontal. Where the throw is vertical, a locking device shall be provided to hold the blades in the open position when so set.




FEEDERS AND MAIN


Essential considerations being adapted or followed.


1. On large installation, one feeder is provided for each floor.


2. In small installations, one or two feeders is satisfactory.


3. Feeder for motor must be separate and independent from the light circuits.


4. Feeders requiring more than 50 mm diameter conduit should not be used.


5.Feeders should be subdivided if there are several bends or offsets because a 50 mm conduit is the largest that could be economically used.


6. Feeders radiating from the distributing panel should be provided each with a properly rated switch and circuit breaker.


7. Good practice dictates that feeders and main shall be installed inside a conduit pipe as it carries high voltage that should be well protected.





GROUNDING PROTECTION



A ground is an electrical connection which may either be intentional or accidental between an electric circuit or equipment and the earth, or to some conducting body that serves in place of the earth. The purpose of grounding a circuit is to fix permanently a zero voltage point in the system. The grounded line of a circuit should not be broken nor fused to maintain a solid and uninterrupted connection to the ground.


Grounding could be accomplished in the following manner:

1. Connection to a buried cold water main.


2. Connection to a rod or group of rods.


3. Connection to a buried ground plate.



THE PANELBOARD



A panelboard is a single panel or group of panel units designed for assembly in the form of a single panel. This includes buses, automatic overcurrent protective devices, and with or without switches for the control of light, heat or power circuit. It is designed to be placed in a cabinet or cutout box placed in or against a wall or partition and accessible only from the front.


Principles applied in installing panel board

1. The approach should be accessible and convenient.


2. The panelboard must be centrally located to shorten the home wiring runs.

3. It must be installed near the load center. As in most cases, panelboard is installed near the kitchen and the laundry where heavy loads are expected.


MAIN- is the feeder interior wiring extending from service switch, generator bus, or converter bus to the main distribution.


BRANCH CIRCUIT- is defined as the circuit conductors between the final overcurrent device protecting the circuit and the outlets. This means that the branch circuit is only the wiring between the circuit overcurrent protection device such as fuses or circuit breaker and the outlets. However, it is a common knowledge and practice that the branch circuit comprises the entire circuit including the outlet receptacles and other wiring devices.



PROTECTION OF THE BRANCH CIRCUIT


Any current in excess of the rated current capacity of the equipment or the rated ampacity of the conductor is called overcurrent.


The causes of overcurrent are:

1. Overload in the equipment conductors.


2. Short circuit or ground fault

As per PEC requirement, conductors shall be protected against overcurrent in accordance with their ampacities (Art. 4.5.1.3)


Ampacity - is the current-carrying capacity of an electric conductor.



CIRCUITRY DESIGN


Circuitry design varies according to the number of designers. However, good circuitry design is based on the following considerations:



flexibility of the circuit

It means that the installation can accommodate all probable pattern arrangements and location of the loads for expansion, or future development

· reliability and efficiency of service

It means to have a continuous service and supply of power that are all dependent on the wiring system.

Reliability of electric power in a facility is determined by two factors:

o utility service

o building electric system

· safety of the circuitry

SAFETY means that independent service can be used in lieu of emergency equipment as backup for normal services. For reliability of the circuitry, the following principles should be considered:

o to provide double emergency power equipment at selected weak points in the system

o that the electrical service and the building distribution system must act together so that the power can reach the desired point of service

o critical loads within the best way to serve them by providing a reliable power either from the outside source, or by standby power package for them

o the system design must readily detect any equipment failure and to be corrected automatically,

· economy as to cost

ECONOMY refers to the initial cost as well as the operating costs. These two cost-factors stand in inverse relationship to one another. OVER DESIGN is as bad as under design. It is wasteful both on initial and operating costs.

The effect of acquiring low cost equipment:

o high energy cost

o higher maintenance cost

o shorter life

· energy consideration

It is a complex one considering the following factors:

o energy laws and codes

o budget

o energy conservation technique

o energy control

· space allocation

It must consider the following:

o easy maintenance

o ventilation

o expandability

o centrality

o limitation of access



BRANCH CIRCUIT

The branch circuit is classified into:

  • General purpose branch circuit

It supplies outlets for lighting and appliances, including convenience receptacles


  • Appliance branch circuit

It supplies outlets intended for feeding appliances.


  • Individual branch circuit

It is designed to supply a single specific item.



·

CIRCUITING GUIDELINES:


There are many ways of doing circuitry but there is no optimum or perfect way of doing it. However, there are certain rules and guidelines promulgated by the NEC for flexibility, economical, and convenient way of installing a circuitry.



1. The Code requires sufficient circuitry to supply residential load of 30 watts per square meter in buildings excluding porches, garages, and basements.

2. The requirement of 30 watts per square meter is up to 80 sq. m for a 20 amperes circuit (2400 watts) or 60 sq. m for 15 ampere circuit (1800 circuit).

3. Good practice suggests that the load should not exceed 1600 watts for a 20 amperes circuit and 1200 watts for a 15 amperes circuit.

a. Observe a minimum load of 1200 watts on a 15 amperes circuit with a maximum area of 40 sq. m

b. A maximum load of 1600 watts on a 20 amperes circuit with a maximum area of 53 sq. m

4. The Code requires a minimum of 20 amperes application branch circuit to feed all small appliance outlets in the kitchen, pantry, dining, and family room

5. The general purpose branch circuit shall be rated at 20 amperes circuit, wired with No. 12 AWG being the minimum size of conductor wire required for all convenience outlets.

6. Plug outlets or convenience receptacles shall be counted in computing the load if it is not included in the load for general lighting circuit. To find the number of outlets for 9 and 12 A loading on a 20 A circuit respectively, we have:


a. For 15 A ckt : 91.5 = 6 outlets

b. For 20 A ckt : 121.5 = 8 outlets

7. Convenience receptacles should be planned properly, so that in case of failure by any one of the circuitry, the entire area will not be deprived of power supply.

8. All kitchen outlets should be fed from at least two of these circuits

9. The Code further stipulated that: “all receptacles are potential appliance outlet and at least two circuits shall be supplied to serve them.”

10. Certain outlets in the room should be designed as appliance outlet like:

a. All kitchen receptacles

b. Dining room receptacles

c. One in the living room

11. The Code requires that, “at least one 20 A ckt. Supply the laundry outlets.”

12. If air conditioner is anticipated, provide a separate circuit for this particular appliance






OTHER GOOD PRACTICES IN CIRCUITING


1. Lighting and receptacles should not be combined in a single circuit.

2. Avoid connecting all building lights on a single circuit

3. Lighting and receptacles should be supplied with current from at least 2 ckt. so that if a single line is out, the entire area is not deprived of power.

4. Do not allow combination switch and receptacle outlets

5. Provide at least one receptacle in the bathroom, and one outside the house. Both must be Ground Fault Circuit Interrupter (GFCI) type

6. Provide switch control for closet lights. Pull chain switch is nuisance

7. Convenience outlet though counted as part of the general lighting load shall be limited to 6 convenience outlets on a 15 A ckt and 8 convenience outlet on a 20 A ckt.

8. The Code requires that, at least one 20 A ckt supply shall be installed to the laundry outlets

9. Convenience outlet shall be laid out in such a manner that no point on a wall is more than 2 meters from an outlet. Use a grounding type receptacle only

6 comments:

  1. Really appreciated your efforts. it's really informative especially for newbies. keep sharing.
    Electrical Building Design

    ReplyDelete
  2. Thank you. It is very informative.

    ReplyDelete
  3. I am very grateful to Dr Dawn Acuna, for bringing back my husband who left me for another woman, that moment my husband Left me I thought I lost everything until a friend of my gave me Dr Dawn Acuna, WhatsApp contact, I messaged her and told her the pain I was going through so she told me that everything was going to be fine that if I have the faith and believe in her that the spell will surely work for me and my husband will surely come back home and she told me what to do, so those things were done and 48 hrs later my husband came back home begging for my forgiveness, am so happy and grateful to Dr Dawn Acuna, if you need her help contact her, she's accurate and sincere,
    * If you want spell to conceive.
    *If you want to get pregnant.
    * If you want to return your lover
    *If you want to cure any kind of sickness
    * If you need spell to get good job. *If you want to stop having miscarriage. And E.T.C. write her on email { dawnacuna314@gmail.com }
    WhatsApp: +2348032246310

    ReplyDelete
  4. Power quality issues can be perplexing and frustrating, but your post simplifies the subject and offers practical solutions. It empowers homeowners and businesses to take control of their power quality and ensure smooth operations.

    ReplyDelete
  5. It's amazing how dependent we are on home appliances, but electrical troubles can really throw a wrench in our daily routines. Learning to diagnose and fix minor issues can be a lifesaver.

    ReplyDelete
  6. Ensuring compliance with legal requirements for outdoor electrical projects is vital, and your post on permits is a great guide. The practical tips you've shared are essential for homeowners looking to navigate this process.

    ReplyDelete